[ Prev ]    Page:   1    2    3    4    5    6    7    8    [ Next ]

PDF version for print


Main Specifications

Module size: 600 mm x 600 mm (24" x 24")

System

AD-600 

CA-400

Height

60 mm (2.36") 

40 mm (1.57")

Cable Trench width

90 mm (3.54") 

90 mm (3.54")

Cable Trench Clearance

55 mm (2.16") 

35 mm (1.37")

Main Components:
UniPanel: made of fire retard, recycled poly-propylene

 

AD-611: size 510 x 510 x 60 mm (20.08" x 20.08" x 2.36")
CA-411: size 510 x 510 x 40 mm (20.08" x 20.08" x 1.74")

Base Connector:

 

Size 169 mm x 169 mm x 15 mm (6.65" x 6.65" x 0.59")
Made of recycled poly-carbonate plus ABS

Central Cap:

 

Size 148 mm x 148 mm (5.82" x 5.82")
2.0 mm (0.08") thick steel, V-shape re-enforced ribs corrosion resistance treatment by electro-deposition, black

Flank Cap:

 

Size 223 mm x 120 mm (8.78" x 4.72")
2.0 mm (0.08") thick steel, V-shaped re-enforced ribs corrosion resistance treatment by electro- deposition, black

Sound Attenuation Blanket: 2.0 mm (0.08") thickness

Accessories
Ramp,
Starting Cap, Edge Rail, Aluminum Ramp Rail, Aluminum Free Standing, Exit-Cap, Edge Trimmer etc., to support quick and efficient installation by least cutting at perimeters.

Surface floor covering: on top of CMS series
Commercial carpet tile: such as Milliken, Interface, Toly…
Commercial rate vinyl tile: thickness>4.0 mm
Hard floorings such as marble, granite, wood, are not suitable.

Environment Friendly
All components of the system, UniPanel (main panel), Base Connector, Central Cap, Flank Cap, Ramp, Aluminum Skirting, and etc., shall be re-usable and 100 percent recyclable.

Tests

Fire Retard
UniPanel: Meet NFPA 253 class A rating as test accordance with ASTM E-648 Critical Radiant Flux. Meet UL 94 V-2, Meet BS 476, Part 7, B2

Concentration Load:
Test in accordance with ASTM-E196 (2" plate)

UniPanel AD-611
: 400 kg<2.5 mm depression
UniPanel CA-411
: 360 kg<2.5 mm depression
Central Cap
: 300 kg<2.0 mm depression
Flank Cap
: 300 kg<2.0 mm depression

Concentration Ultimate Load:
AD-611
UniPanel>700 kg
CA-411
UniPanel>600 kg

UniForm Ultimate Load:
AD-611
UniPanel>200 psi
CA-411
UniPanel>150 psi

Warranty: 5 years warranty (except when product is subject to abuse, negligence, abnormal use and not under Netfloors installation instruction).

 

 

 

In pursuing of quality improvement, the manufacturer reserves the rights to vary specifications without prior notice.


Patent granted - The System

Japan: Utility Model No.3032638
Australia: Invention Patent No.679415
France: Invention Patent No.97 99 255
Taiwan: Invention Patent No.127700
South Africa: Invention Patent No.97/020 

USA: Invention Patent No.5.630.300
Germany: Utility Model No. 29520105.5
U.K.:Invention Patent No.2309042
China: Utility Model No. ZL 02 2 91689.X

Patent pending ------ V-shape re-enforced steel cap system

World-wide patent pending

visit us at
www.net-floor.com
   |   www.net-floor.biz

 

[ Prev ]    Page:   1    2    3    4    5    6    7    8    [ Next ]